Minimum circuit ampacity breaker size

The minimum circuit ampacity breaker size depends on several factors, including:

  1. Circuit load: The total current drawn by the devices connected to the circuit.
  2. Circuit voltage: The voltage at which the circuit operates.
  3. Circuit length: The distance between the source of power and the farthest point on the circuit.
  4. Circuit type: The type of circuit (e.g., residential, commercial, industrial).
  5. National Electrical Code (NEC): The minimum breaker size required by the NEC.

Here are some general guidelines for determining the minimum circuit ampacity breaker size:

Residential Circuits (NEC Article 220.12)

Commercial and Industrial Circuits (NEC Article 220.12)

Circuit Load Calculation

To determine the minimum circuit ampacity breaker size, you need to calculate the total load on the circuit. This includes the sum of the current drawn by all devices connected to the circuit.

For example, if you have a circuit with:

The total load on the circuit would be: 1.66A + 10A + 12.5A = 24.16A

In this case, you would need a minimum 25-ampere breaker to accommodate the total load.

Additional Considerations

Remember to always consult the NEC and local electrical codes for specific requirements and guidelines for determining the minimum circuit ampacity breaker size. It's also recommended to consult with a licensed electrician if you're unsure about the minimum breaker size for a particular circuit.