Electrical breaker wire size chart
Here is a wire size chart for electrical breakers:
Breaker Size Chart
Breaker Amp Rating | Wire Size (AWG) | Wire Size (mm²) |
---|---|---|
15A | 14 | 1.5 |
20A | 12 | 2.5 |
30A | 10 | 4 |
40A | 8 | 6 |
50A | 6 | 10 |
60A | 4 | 16 |
80A | 2 | 25 |
100A | 1 | 35 |
150A | 0 | 50 |
200A | 00 | 70 |
Notes:
- AWG (American Wire Gauge) is a standard unit of measurement for wire size.
- mm² is the metric equivalent of AWG.
- The wire size chart is based on the National Electric Code (NEC) and is intended for use in the United States.
- The wire size required for a breaker is determined by the breaker's amp rating and the distance the wire will be run.
- It's always a good idea to consult the manufacturer's instructions for specific wire size recommendations for your breaker and electrical system.
Wire Size Calculation:
To calculate the wire size required for a breaker, you can use the following formula:
Wire Size (AWG) = (Breaker Amp Rating x Distance in Feet) / 0.03
For example, if you have a 30A breaker and you need to run the wire 100 feet, the wire size would be:
Wire Size (AWG) = (30A x 100 ft) / 0.03 = 10 AWG
This means you would need to use a 10 AWG wire for the 30A breaker.
Remember to always follow the manufacturer's instructions and local electrical codes when selecting wire size for your electrical system.